|
 |
|
Menu |
|
AUTOMATIC
VOLTAGE
STABILISERS |
|

Series

|
|
Automatic Voltage Stabilisers |
|
Electrodynamic Stabilizers with Digital Control |
|
DESCRIPTION OF THE UNIT
The stabilising system is designed to
operate with rated voltage in accordance with IEC 38 and is expected to
be
connected between main power supply and load.
The purpose is to supply the loads a stabilised voltage having an input
voltage variable with respect to the rated
value. The highest input current is obtained with the minimum rated
voltage; as the output voltage is stabilised
within a close range, the output current is considered to be constant.
Stabilisation takes place on the ‘rms’ value of the voltage and is not
affected by harmonic distortion in the mains.
The stabiliser can operate with a load variation range from 0 to 100%;
the response time depends on the input
voltage percentage variation and on the type of design (indicatively, it
can vary between 8 and 24msec/V).
The voltage stabiliser is not affected by the load power factor and
since regulation is performed without chopping the
voltage sine wave, neither appreciable harmonic distortion nor phase
displacement is introduced on the downstream
line.
The equipment is housed in a metal enclosure with RAL7035/RAL7032 finish
and IP21 protection class. Depending on
the type, the stabilisers can be air-cooled (natural or aided convection)
or oil-cooled.
When the input variation percentage is –25%, -30% or –45% the unit is
provided with a special component (super
capacitor) able to adjust automatically the output voltage to the
minimum value after a failure in the mains.
Such device prevents from possible damages to the user due to the
potentially high voltages that might occur when
the rated supply is re-established.
MAINS COMPONENTS
The main components of the
stabiliser are:
Buck/boost
transformer
The buck/boost transformer is a
standard dry-type transformer; the secondary winding is connected in
series to the mains while the primary winding is supplied by the voltage
regulator.
Voltage regulator
The voltage regulator consists of
an autotransformer with continuously variable transformer ratio. The
voltage intake varies depending on the contact position; therefore the
voltage supplied to the transformer primary winding also varies. The
voltage across the regulator contacts (and consequently that on the
secondary winding of the buck/boost transformer) is either in phase or
in opposition to the supply voltage, and it is therefore added or
subtracted to the supply voltage, thus compensating its variations
Auxliary Circuit with Microprocessor
The DSP
microprocessor-based control circuit (specific for fully digital drives)
compares the output voltage value to the adjusted one. When the
percentage variation is too high, the control drives the voltage
regulator gearmotor. By doing so the regulator rollers change their
position thus varying the voltage drawn and supplied to the buck/boost
transformer primary winding.
All the described activities are
performed automatically
The voltage stabiliser can operate
with input and output voltages different from the rated voltage. Such
setting can be performed at the factory or at the Customer's premises by
adjusting the dip-switch mounted on the electronic control card within
the allowed range and according to the instructions described in the
handbook. In the SIRIUS and TAURUS stabilisers, such setting can be
performed by communicating directly with the microprocessor from a PC
(through an RS232 interface). If the rated output voltage differs from
the input voltage, a suitable step-up or stepdown autotransformer should
be installed in the equipment. However the voltage stabiliser can work
just as well after accepting that the range of input voltage variation
is not symmetric. |
|
Importance of Voltage Stabilisers |
|
The
correct operation of the majority of electrical and electronic equipment
depends on the supply voltage accuracy and stability.
Nowadays, many industrial, commercial and private users are subject to
long-lasting fluctuations that can be inconvenient or even dangerous.
More
recently, dramatic voltage drops or blackouts have occurred due to low
energy production coinciding with high demand. The voltage stabiliser
has proved to be an effective device to prevent potential damage caused
by input voltage fluctuactions.
Installing a voltage stabiliser is often the solution to ensure
continuity and quality of production. |
|
Comparison with a UPS System |
|
The type of
utilisation described before pushes towards the choice of a voltage
stabiliser instead of a UPS in order to have:
 |
Lower costs |
 |
High power availability |
 |
Wider input variation ranges |
 |
Overload capacity up to 2In |
 |
Inrush current capacity up to 10In |
 |
Higher reliability and ruggedness |
 |
Absence of batteries and consequent easy
storage and handling |
 |
Negligible harmonic distortion because of
the use of electronic components only in auxiliary circuits |
 |
Service continuity |
|
|
Applications |
|
Typical
uses include:
 |
laser
cutting machines |
 |
computers |
 |
assemblies with electronic drive |
 |
testing facilities |
 |
food &
drink industry |
 |
private homes with installed power (pools, air conditioning units,
lifts, etc,.) |
 |
special instrumentation |
|
|
Use of a Voltage Stabiliser |
|
A typical voltage stabiliser is
able to respond to changes in voltage level called sags (voltage
drops) and surges (voltage
peaks) on the input line.
Sags might be due to undersized
distribution lines, connection of large loads to the network, ground
faults.
Surges might be generated by
disconnection of large loads, increased voltage at the generating plant,
atmospheric events.
The duration of such phenomena
depends on the cause and is not easily predictable.
Sags are generally more common,
especially where the distribution is not wide and efficient.
Other disturbances like spikes,
transients, high frequency noise and harmonic distortion have to be
treated with the addition of specific filtering systems.
The good functioning of the
majority of electrical and electronic equipment depends on the supply
voltage correctness and steadiness. Nowadays, many industrial and
private users are subject to long-lasting fluctuations that can be
inconvenient or even dangerous |
|
Come scegliere
uno stabilizzatore di tensione |
|
Generally speaking, a stabiliser can be chosen on the basis of a few
elements:
Number of
phases
The
number of phases depends on the type of load:
One
single-phase load:
single-phase stabiliser, regardless of the nature of the system where
the load is installed.
Combination of several single-phase loads:
3-phase stabiliser with independent regulation on each phase or a
single-phase stabiliser on each load.
Three-phase loads:
3-phase stabiliser with independent regulation on each phase or 3-phase
stabiliser with regulation averaged across the three phases.
Rated Voltage
Always detect the
nominal voltages that are supposed to be present at the input and at the
output of the stabiliser. In case of 3-phase systems, provide with the
line-to-line voltage value.
Since there are
different nominal voltages around the world, do not assume that YOUR
nominal voltage is automatically known.
The standard voltage
stabiliser can operate with the following rated voltage:

Input variation range
It’s a key information for the
choice and the design of the stabiliser.
Establish the nature of the
oscillation of the input voltage and always keep a safety margin on
such percentage. The standard production can include stabilisers for
symmetrical and asymmetrical input variation range. If the input voltage
variation goes beyond the rated range, the difference between real and
rated variation is transferred onto the output.

Type of regulation
Three-phase voltage regulation can be performed in two different ways:
independently on each phase. Used for 3-phase loads and 1-phase loads
with up to 100% unbalance and unbalanced input voltage. In this
configuration the voltage stabiliser requires the neutral wire.
averaged on the three phases. Used for 3-phase loads and 2-phase loads
with maximum 50% unbalance and balanced input voltage. In this
configuration the voltage stabiliser does not require the neutral wire.

Rated Power
E stablish
the power required to supply your load system and allow for an extra
safety margin for possible future extensions.
A voltage stabiliser power is
expressed in kVA (kilovoltamperes), whilst load power is often given in
kW (kilowatts). The link between these two measuring units is provided
by the power factor (cosφ):
kVA = kW/cosφ
Remember that:
kVA = load voltage x load current (single-phase)
kVA = √3 x phase to phase load voltage x load current (three-phase)
If the power factor or the load
power in kW cannot be easily established, measure the absorbed currents
in order to allow for a correct design of the stabiliser.
All the stabilisers are designed
for the maximum input current.
Installation
In order to provide
with the best machine, it is recommended to inform about the
installation condition. It is necessary to know:
 |
IP protection degree |
 |
Indoor or outdoor installation |
 |
Installation site altitude and climatic
properties |
 |
Ambient temperature |
 |
Possible environmental hazards such
aggressive atmosphere, exposure to chemical components and so on. |
Advantages
Choosing an electromechanical voltage stabiliser means:
 |
Smooth and reliable regulation |
 |
Up to ±0.5% output accuracy |
 |
Admitted inrush current up to 10In |
 |
Negligible introduction of harmonic
distortion |
 |
High efficiency |
 |
High ratings |
|
|
MINI AVR |
|

The MINI AVR voltage stabiliser covers the power rating range between
0.3kVA and 150kVA and allows for the choice of several input voltage
variation percentages within a broad range (from +30% up to -45%).
For ±15%, ±20%, ±25 and ±30% range
the change of stabilisation is obtained through different internal
connections.
Fuses or automatic circuit
breakers are provided on the regulation circuit to protect against
overload and short circuit on the voltage regulator. The auxiliary
circuit is protected by fuses.
Where provided, a buzzer is
activated whenever an overload condition occurs.
In the lower rating types, a pilot
light that indicates when the stabiliser is connected to the mains in
mounted on the front. For higher ratings, the stabiliser is provided
with a multi-task digital network analyser. Such instrument is
able to provide with information regarding the status of the line
downstream the voltage stabiliser such as phase and linked voltages,
current, power factor, active power, apparent power, reactive power,
etc.
The logic control is based on a
microprocessor. |
|
MINI AVR
Standard Features |
|
Frequency |
47/65 Hz |
|
Admitted load variation |
from 0 to 100% |
|
Mains waveform distortion increment |
<0,2% |
|
Cooling |
Natural air - Aided air |
|
Ambient temperature |
-15/+45°C |
|
Storage temperature |
-25/+60°C |
|
Relative Humidity |
95% |
|
Admitted overload |
200% 2 min. |
|
Colour |
RAL 7032 |
|
Protection |
IP 21 |
|
Installation |
Indoor |
|
Rating in relation to the input
variation percentage |
|
±15% |
±20% |
±25% |
±30% |
-25/+15% |
-35/+15% |
-45/+15% |
|
1 |
0,7 |
0,5 |
0,3 |
0,7 |
0,5 |
0,3 |
|
2,5 |
2 |
1,5 |
1 |
2 |
1,5 |
1 |
|
5 |
4 |
3 |
2 |
4 |
3 |
2 |
|
7 |
5 |
4 |
3 |
5 |
4 |
3 |
|
10 |
7 |
5 |
4 |
7 |
5 |
4 |
|
15 |
10 |
7 |
5 |
10 |
7 |
5 |
|
20 |
15 |
10 |
7 |
15 |
10 |
7 |
|
25 |
20 |
15 |
10 |
20 |
15 |
10 |
|
35 |
25 |
20 |
15 |
25 |
20 |
15 |
|
45 |
35 |
25 |
20 |
35 |
25 |
20 |
|
60 |
45 |
35 |
25 |
45 |
35 |
25 |
|
75 |
60 |
45 |
35 |
60 |
45 |
35 |
|
100 |
75 |
60 |
45 |
75 |
60 |
45 |
|
150 |
100 |
75 |
60 |
100 |
75 |
60 |
|
Any other variation range not mentioned
in the table above can be dealt with on request |
|
MINI AVR ±15% Automatic
Single-Phase Voltage Stabiliser |
|
Type |
Rated
Power
kVA |
Input
Voltage
±15%
V |
Max
Input
Current
A |
Output
Voltage
±1%
V |
Rated
Output
Current
A |
Efficiency
% |
Respose
Time
ms/V |
Dimensions
LxWxH
mm |
Weight
kg |
|
MINI AVR
111-15 |
1 |
230 |
5 |
230 |
4 |
>94 |
16 |
275x425x260 |
15 |
|
MINI AVR
113-15 |
2,5 |
230 |
13 |
230 |
11 |
>96 |
16 |
275x425x260 |
22 |
|
MINI AVR
115-15 |
5 |
230 |
25 |
230 |
22 |
>97 |
16 |
275x425x260 |
40 |
|
MINI AVR
117-15 |
7 |
230 |
35 |
230 |
31 |
>98 |
16 |
300x565x280 |
42 |
|
MINI AVR
119-15 |
10 |
230 |
51 |
230 |
44 |
>98 |
16 |
300x565x280 |
50 |
|
MINI AVR
121-15 |
15 |
230 |
77 |
230 |
65 |
>98 |
16 |
300x565x280 |
55 |
|
MINI AVR
123-15 |
20 |
230 |
102 |
230 |
87 |
>98 |
18 |
405x670x1150 |
80 |
|
MINI AVR
125-15 |
25 |
230 |
128 |
230 |
109 |
>98 |
18 |
405x670x1150 |
100 |
|
MINI AVR
127-15 |
35 |
230 |
179 |
230 |
152 |
>98 |
18 |
405x670x1150 |
120 |
|
MINI AVR
128-15 |
45 |
230 |
230 |
230 |
196 |
>98 |
18 |
605x850x1450 |
260 |
|
MINI AVR
129-15 |
60 |
230 |
307 |
230 |
261 |
>98 |
18 |
605x850x1450 |
300 |
|
MINI AVR
131-15 |
75 |
230 |
384 |
230 |
326 |
>98 |
18 |
605x850x1450 |
380 |
|
MINI AVR
133-15 |
100 |
230 |
511 |
230 |
435 |
>98 |
18 |
605x850x1650 |
450 |
|
MINI AVR
135-15 |
150 |
230 |
767 |
230 |
652 |
>98 |
18 |
605x850x1650 |
530 |
| |
|
MINI AVR ±20%
Automatic Single-Phase Voltage Stabiliser |
|
Type |
Rated
Power
kVA |
Input
Voltage
±20%
V |
Max
Input
Current
A |
Output
Voltage
±1%
V |
Rated
Output
Current
A |
Efficiency
% |
Respose
Time
ms/V |
Dimensions
LxWxH
mm |
Weight
kg |
|
MINI AVR
111-20 |
0,7 |
230 |
4 |
230 |
3 |
>94 |
12 |
275x425x260 |
15 |
|
MINI AVR
113-20 |
2 |
230 |
11 |
230 |
9 |
>96 |
12 |
275x425x260 |
22 |
|
MINI AVR
115-20 |
4 |
| |