Contactors
Each bank of capacitors is controlled by a three-pole contactor. To
limit the inrush current peaks with reactors.
Rated voltage of auxiliary circuits: 110 Vac, 50 Hz
Fuses
Each bank of capacitors is protected by a set of three fuses (NH00 type)
with high breaking capacity. Also the auxiliary circuits are protected
by fuses.
Capacitors
Self-healing metallized polypropylene single-phase capacitors, equipped
with overpressure safety device and discharge resistor. Filling:
biodegradable non toxic dry type, PCB free. Delta connection.
VRC
550 Vac Series, IMQ approved.
Capacitance tolerance: -5% +10%
Dielectric losses: <0.3W/kvar
Temperature class: -25/D (55°C)
Blocking Reactors
Tuning frequency: 180 Hz
(3.6 = 7.7%)
Regulator
Varmetric measurement by means of a C.T. (secondary 5A) not supplied
Reference Standards
Comply with L.V. 73/23 (93/68) EEC Directive
Capacitors: CEI EN 60831-1/2
Equipment: CEI EN 60439-1
Options (on request)
Protection and Control Instrument SPC2
Protection Degree: IP40 - IP54
L type: cable entry from the top