1.00
CONTROLLER MANUAL
1.01 GENERAL CHARACTERISTICS
· Digital
microprocessor power factor controller
· TTL-RS232
serial interface for set-up and automatic testing via PC (Personal
Computer)
· Internal
temperature sensor
· Advanced
functions for capacitor current overload measurement, average weekly
power factor, maximum value logging
· 2
relays programmable as alarm and/or fan control
1.02
FRONT PANEL

1.03 INSTALLATION
Install the controller according to wiring
diagrams.
The CT (Current Transformer) must be connected to the free phase, i.e.
not
on phases used to supply the unit, as indicated in the wiring diagrams.
The controller automatically recognizes the
CT current flow. In case of co-generation systems, disable this function
(refer to “Advanced menu” section 1.18 “ADVANCED MENU SETTINGS”) and
connect the CT correctly.
The CT secondary must be earthed/grounded.

IMPORTANT!
For
three-phase connection, the voltage input must be connected phase to
phase;
the current transformer must be connected on the remaining phase.
The polarity of the current/voltage input is indifferent.
WARNING! Disconnect the line and the supply when operating on terminals.
1.04
POWER UP
At
the first power up, the display shows
---
which means no parameter has been programmed yet.
Under
these conditions, a manual test of the steps can
be conducted to check the connections.
Press the
+
or
–
key to connect or disconnect the steps.
WARNING!
During this phase, the step control is totally manual and the unit does
not control the reconnection time to allow the capacitors to discharge.
1.05
PARAMETER SET-UP
There are various methods of setting parameters and commissioning the
controller to operate properly, namely:
· Section
1.06 MANUAL KEYPAD SET-UP
· Section
1.09 QUICK SET-UP VIA PC
· Section
1.11 AUTOMATIC SET-UP
1.06 MANUAL KEYPAD SET-UP



1.07 TABLE OF BASIC MENU PARAMETERS

1.08 DESCRIPTION OF BASIC MENU PARAMETERS
P.01 -
CT primary current
For values higher than 1000, a flashing dot indicates “thousands”.
P.02 -
Smallest step kvar
Rated power in kvar of the smallest installed capacitor bank.
Example: For 10 kvar, set 10.0
P.03 -
Rated capacitor voltage
Rated voltage (nameplate) of the capacitors.
Example: For 460V, set
460
P.04 -
Reconnection time of the same step in seconds
Minimum time needed for the capacitor to discharge and be ready to be
used again.
Example: For 60 seconds, set
060
P.05 -
Sensitivity
The sensitivity is a coefficient, which allows adjusting the controller
operating speed. A low sensitivity provides faster adjustments but with
a greater number of switchings. With high sensitivity, the regulation is
slower but with fewer switchings.
The sensitivity value corresponds to the time the controller waits
before responding to a
reactive power demand which is equal to the smallest step (kvar). For
higher power demands, the time will be quicker according to the criteria
of inverse proportion.
Example: For 60 s/step, set
060
In
this case with the smallest bank of 10kvar (P.02 = 10.0) and a system
demanding 20kvar to achieve the set cosj
(Dkvar
= 20), the controller will wait for 60/2 = 30 seconds before beginning
the capacitor connection procedure (indicated by the flashing AUT LED).
P.06 LED 1...n Step coefficients
The coefficients of the steps represent the power rating of each step in
relation to the smallest capacitor bank, whose value is programmed at
P.02.
If a step has the same power rating of the smallest step, then its
coefficient will be 1, while if it is double it will be 2 and so on up
to a maximum of 16. By setting 0, the step will be disabled and will
never be considered or used by the controller. The last two steps can be
programmed to operate as normal steps or as alarm relay or again as fan
control. If the penultimate step is linked to a function then the last
step cannot be used as a normal step.
To
select these functions, press
-
until the following codes are viewed:
noA
= Normally open alarm (contact open in absence of alarm)
ncA =
Normally closed alarm (contact closed in absence of alarm)
FAn
=
Fan control
N.B. For the alarms, see table on page 41. For fan control, refer to
pages 36 and 38.
Example: With a PFC7 installed in a control panel with 6 capacitor banks,
5, 10, 20, 20, 20, 20 kvar respectively at rated 460V and the last step
is to be used as alarm, the parameters must be programmed as follows:
P.02 = 5.00
(Smallest
step = 5kvar)
P.03 = 460
(Rated
voltage 460V)
P.06
LED 1 = 001 (5 kvar = 1 times P.02)
P.06
LED 2 = 002 (10 kvar = 2 times P.02)
P.06
LED 3 = 004 (20 kvar = 4 times P.02)
P.06
LED 4 = 004 (20 kvar = 4 times P.02)
P.06
LED 5 = 004 (20 kvar = 4 times P.02)
P.06
LED 6 = 004 (20 kvar = 4 times P.02)
P.06
LED 7 =
noA
(Normally
open alarm)
1.09 QUICK SET-UP VIA PC
For quick set-up via PC, it is necessary to use the relative automatic
test and remote control software that includes the PC software and the
connection cable. For this reason, all the controller models are
provided with a communication port at the rear. All parameters are
displayed on the PC monitor. The settings can be transmitted and stored
with a few simple clicks of the mouse.
If
a number of controllers must be programmed with the same settings, the
set-up can be downloaded on a file and reused later by programming all
the parameters with maximum ease and security.
For use of the programming software, see Chapter 2.
1.10
RAPID CT SET-UP
When the CT to be used at the moment of the installation is not known,
the parameter
P.01
for CT primary current can remain set to
OFF
while all the others can be programmed.
In
this case during the system installation and once the controller is
powered up, the display will view a flashing
Ct
(Current Transformer). The CT primary can be set directly by pressing
+
and
-.
Once programmed, press
MAN/AUT
to confirm. The unit will store the setting and directly restart in
automatic mode.
1.11
AUTOMATIC SET-UP
CAUTION!
Never use if a complete panel has been purchased.
The setting is useful if it is not possible to access the C.T. or else
when the characteristics of the capacitor banks are not known.
The automatic set-up of parameters allows the unit to be placed in
service without having to program any parameter.
To
activate the automatic set-up when the unit is in MAN or
---
mode, simultaneously press
MODE
and
MAN/AUT
keys for 5 seconds.
The wording
ASE
(Automatic
Set-up) flashes indicating that the automatic set-up of the parameters
is in progress.
The procedure will last a few minutes during which the controller
measures the power rating of the connected steps. This measurement will
then be continuously updated during the normal operation.
If
the load of the system varies frequently, the same step may have to be
measured several times. In this case, the procedure may last longer.
At
the end of the automatic set-up, the controller is ready for automatic
operation.
IMPORTANT!
It is recommended to
avoid substantial current variations as much as possible during the
automatic set-up. During this automatic set-up, the controller is not
able to monitor certain data such as CT primary current, rated capacitor
voltage.
Therefore we shall have
as follows:
· The
current cannot be viewed in Amperes but only as a percentage.
· The
Dkvar and Skvar measurements are not available.
· The
measurement and protection for capacitor overload are not accessible.
· All
of the relays are considered as normal capacitors banks. So no alarm
relay or fan control configuration is possible.
· The
capacitors installed must be with a power rating which is a multiple of
1, 2, 4, 8 or 16 times the smallest capacitor step.
· The
unused steps must be placed at the higher step numbers.
Note: After termination of the automatic set-up, if access is gained in
manual mode to setting the parameters, the controller will consider all
the parameters present as valid. Therefore, all of the measurements and
functions will be available once again.
1.12
DISPLAY OF MEASUREMENTS AND REQUIRED COSj
SETTING
Normally,
the display shows the cosø of the system together with the IND and CAP
LED’s. The flashing decimal point indicates the negative sign (inverse
energy flow).
By
pressing the
MODE
key, the V, A, Dkvar, etc. LEDs are switched on one after another and
the relative measurement of each is shown.
An
optional function is available for each LED and indicated on the front
panel, which can be displayed by pressing the
+
and
-
keys (the LED flashes quickly thereafter).
When the SET COSj LED lights up, the set-point of the required cosj can
be programmed; the
+
and
-
keys increase or decrease the value respectively. The set cosj can be
adjusted between 0.80 IND and 0.80 CAP.
The following table summarises all the available measurements.

1.13 MAXIMUM VALUE CLEARING
The maximum values of Voltage, Current, Overload and Temperature along
with average weekly power factor can be cleared by simultaneously
pressing the
+
and
-
keys for 3 seconds. Once clearing is complete, the display views
CLr.
1.14 OPERATING MODE
The AUT and MAN LED’s indicate the automatic or manual operating mode.
To
change mode, press the
MAN/AUT
key for at least 1 second.
When the SET COSj
LED is lit up, no mode change is possible.
The operating mode remains stored even if power is removed.
1.15 MANUAL OPERATION
When the controller is in manual mode, one of the steps can be selected
and manually connected or disconnected. If a measurement other than cosj
is viewed, press
MODE
until all the LED’s of the measurements go out.
To
select one of the steps, use the
+
and
-
keys. The LED of the selected step starts flashing quickly. Press
MODE
to connect or disconnect the selected step. If the reconnection time of
the selected step has not elapsed, the MAN LED flashes to indicate the
operation has been confirmed and will be conducted in due time.
The manual configuration of the steps is maintained even when voltage is
removed. When power returns, the original state of the steps is restored.
1.16
AUTOMATIC OPERATION
In
automatic mode, the controller calculates the optimum configuration to
achieve the set cosj
value.
The selection criteria take into consideration many variables such as:
power rating of each step, the number of operations, the total time of
usage, reconnection time, etc.
The controller displays the imminent connection or disconnection of the
step by the AUT LED flashing. The LED flashing can last in cases when
the connection of a step is not possible because of the reconnection
time (i.e. capacitor discharge time).
1.17 KEYPAD LOCK
It
is possible to enable a function to exclude any modification to the
operating parameters, however viewing of the measurements is still
provided.
To
lock and unlock the keypad, press and hold down the
MODE
key. Next press the
+
key three times and the
-
key twice, then release
MODE.
The display will show
LOC
when the keypad is locked and
UnL
when unlocked.
When the lock is enabled, it is not possible to make the following
operations:
· Change
from automatic and manual mode
· Access
set-up menus
· Change
the cosj
set-point
· Clearing
of MAX values.
When attempting to perform the above operations, the display will show
LOC
to
indicate the locked keypad state.
1.18 ADVANCED MENU SETTINGS
With the controller in MAN mode, press the
MODE
key for at least 5 seconds.
The wording
SEt
will appear to indicate access to basic menu parameters.
At
this point, simultaneously press the
+
and
-
keys for 5 seconds until
AdS
appears on the display to indicate access to advanced menu parameters.
1.19 ADVANCED MENU TABLE OF PARAMETERS

1.20 DESCRIPTION OF ADVANCED MENU
PARAMETERS
P.11 -
Type of connection
Programs either single-phase or three-phase connection.
P.12 -
CT connection recognition
When set to Automatic, the controller operates in 2 quadrants and at
power on, it recognizes direction of current flow in the C.T.
When set to Direct, the controller operates in 4 quadrants and can be
used both in normal or co-generation systems. It is however necessary to
check the correct CT connection by making sure the decimal point of the
cosj measurement is not flashing with energy import
conditions. If not, the CT connections (S1 and S2 terminals) must be
inverted or more simply set Inverse.
WARNING!
Before disconnecting the S1 and S2 terminals, check that the CT
secondary terminals are shorted.
P.13 -
Mains frequency recognition
Automatic selection, fixed 50Hz or fixed 60Hz.
P.14 -
Step power adjustment
When this function is enabled and during normal operation, the unit
allows automatic measurement of the power rating of the steps and
modification of the operating parameters in case the steps are worn
(i.e. by making many operations).
Note:
· When
this function is used, the time between the connection of one bank and
the next is 20 seconds.
· If
the automatic set-up is used, the function is automatically enabled.
P.15 -
Standard or Band regulation mode
In
Standard mode, the controller adjusts the system cosj to the set value.
In Band mode, the capacitors are connected when the system cosj is lower
than the set value and are disconnected when in capacitive conditions.
The Band mode is used to further reduce the number of capacitor
connections and disconnections.
Note: The Band mode configuration does not allow programming of
capacitive cosφ.
P.16 -
Standard or Linear connection mode
In
Standard mode, the controller freely selects the steps according to the
logic described in the Automatic operation section above. In Linear
mode, the steps are connected only by progression from left to right
following the step number and according to the LIFO (Last In First Out)
logic. The controller will not connect a step when the system steps are
of different power ratings and by connecting the next step, the
set-point value would be exceeded.
P.17 - Co-generation cosj
set-point
This parameter is programmed when a 4-quadrant
operation is required, i.e. when the system is in the condition of
consuming or producing energy. When the parameter is set to
OFF,
the cosj set-point is the only one and corresponds to the value
programmed with SET COSj (see page 36). On the other hand, when it is
set to a numeric value then the set-points are two: under normal
conditions (system consumes mains energy, positive cosj), the set-point
value is considered as programmed by SET COSj.
Under co-generation conditions (system produces energy, negative cosj),
it is used as programmed to
P.17.
P.18 - Disconnection sensitivity
With this parameter at
OFF,
the sensitivity value set to
P.05
(see basic menu) adjusts the reactive speed during both the connection
and disconnection phases. However, if
P.18
is set to a different value, the programmed value of
P.05
is considered for the connection while the value
P.18
is used for the disconnection of the steps.
P.19 - Step disconnection at change to MAN mode
When this parameter is enabled, the connected steps are disconnected in
sequence when changing from AUT to MAN mode. At the end of the
disconnection, the normal manual mode function is restored.
P.20 - Capacitor overload alarm threshold
By
using this parameter, it is possible to adjust the tripping threshold of
alarm Capacitor Overload. The percentage of current flowing in the
capacitors (calculated by the waveform of the phase voltage) is compared
with this threshold. If the threshold value is exceeded, after the delay,
the alarm is generated and the steps disconnected.
P.21 - Overload threshold for immediate step disconnection
When the measured overload exceeds the value set at
P.21
, the capacitors are immediately disconnected and the capacitor overload
alarm
A07
is generated.
Note: The delay time of Capacitor overload alarm
A07
operates inversely proportional to the overload
entity, compared to the programmed thresholds of
P.20
and
P.21.
When the overload is lower than the
P.20
threshold, the alarm will not be generated. When the overload is equal
to P.20,
the delay time is equal to the one set for the alarm (3 minutes by
default but can be changed via the PC). As the overload increases, the
delay time becomes proportionally less until it attains zero once the
value set to
P.21
is reached. With
P.20
at OFF,
there is no tripping until the value
P.21
is exceeded and the immediate disconnection of the steps takes place.
With
P.21
at
OFF,
the delay TIME is also constant. With
P.20
and
P.21
both at
OFF,
the capacitor overload measurement is disabled as well as the alarm
A07.
In these conditions, the display indicates
---
instead of the overload measurement. Whenever the capacitor banks are
equipped with inductances to prevent harmonic overload,
P.20
and
P.21
must be at
OFF
.
P.22 -
Overload event counter clear time
Each time an
A07
Capacitor overload alarm is generated, the event is registered by an
internal counter, which can be consulted by pressing the
+
key when the OVERLOAD % LED is lit up. The counter indicates the number
of capacitor overload events that have taken place over the time period
defined by
P.22.
This parameter also defines the number of hours during which the events
remain stored. If no event has taken place during the set time period,
the counter is cleared.
P.23 - Overload alarm reset time
Time period during which the
A07
Capacitor overload alarm remains active even though the overload value
has decreased below the alarm thresholds.
P.24 - Unit of measure for temperature
This defines the unit of measurement, in degrees Celsius or Fahrenheit,
for displaying the temperature and the threshold settings related to it.
P.25
-Fan start temperature
Sets the temperature above which the fan relay is activated (if
programmed in one of the last two steps).
P.26
-Fan stop temperature
Sets the temperature below which the fan relay is disactivated (if
programmed in one of the last two steps).
P.27 -
Temperature alarm threshold
Sets the temperature above which the Temperature too high alarm
A08
is
activated.
1.21
ALARMS
When the controller detects an abnormal situation in the system, a
flashing alarm code is displayed. By pressing any key, display of the
alarm will be momentarily ignored to allow the user to check all the
measurements. If no key is pressed for 30 seconds and the alarm
conditions persist, the alarm code will be displayed once again.
Each alarm can cause diverse results such as the alarm relay tripping,
the delayed or immediate step disconnection, etc., according to the
programmed property. The property of each alarm can be changed (e.g.
disabled, change the delay time or effect), by using a PC and the
relative software, used for the quick parameter set-up.
The following table indicates the alarm codes and the relative meaning
of each along with the default setting.
Note:
None of the above-indicated alarms are non-volatile.
In
MAN mode the steps disconnection takes place only for the
No
voltage release (micro-breaking) alarm A09 - No-voltage release.
A01 - Under compensation
Capacitors are all connected and cosj is lower than the set-point value.
A02 -
Over compensation
All capacitors are disconnected and cosj
is
higher than the set-point value.
A03 -
Low current
Current value is lower than 2.5% full scale value. In automatic, the
capacitors are disconnected after 2 minutes of the alarm activation.
A04 -
High current
Current value is 120% higher than full scale value.
A05 -Low
voltage
Voltage value is -15% lower than lower rated voltage.
A06 -
High voltage
Voltage value is +10% higher than higher rated voltage.
A07 -
Capacitor overload
Current value flowing in the capacitors is higher than the set threshold
(refer to
P.20
and
P.21
of advanced menu).
A08 -
Overtemperature
Internal temperature value is higher than the set threshold (refer to
P.27
of advanced menu).
A09 -
No-voltage release
Voltage failure duration is more than 8ms.
1.22
TECHNICAL CHARACTERISTICS

1.24 EXTERNAL DIMENSIONS AND PANEL CUT-OUT

2. PROGRAMMING SOFTWARE MANUAL
2.01 FOREWORD
The programming software allows connection of a controller to a PC via a
serial port RS232.
Thanks to this software the tasks of presetting set-up parameters and
functional check of the power factor correction panel are quicker and
easier. The software is also very useful in trouble shooting as all the
measurements and dimensions can be easily monitored by the operator.
Above all, the following functions are available:
· Graphic
display of all the measurements supplied by the unit with numeric
indication and bar-graphs.
· For
each step:
· Display
of the status (ON/OFF)
· Display
of the function (step/alarm/fan)
· Display
of the preset power
· Display
of the number of operations
· Display
of the total step operating time
· Commands
for manual closing/opening
· Access
to the Basic Setup and Advanced Setup menus
· Access
to the alarm properties
· Possibility
of saving/loading/printing the setup settings
· Display
via virtual front panel with provision for actuating the buttons
· Switching
from manual/automatic modes
· Keypad
lock function
2.02
MINIMUM CONFIGURATION REQUIREM