Menu |
|
POWER FACTOR CORRECTION
FIXED |
|

Series
 |
|
POWER FACTOR CORRECTION FIXED
EQUIPMENT
400 Vac 50 Hz THDI<25% Capacitors MFA 440 Vac
|
|
Rated Voltage
400
Vac – Max Overvoltage 1.1 Un
Max Overcurrent 1.3 In
Rated Frequency
50
Hz
Rated Power
Referred to rated frequency and voltage
Working Temperature Range
-25°C/+50°C
Cubicle
20/10mm sheet steel, protected against corrosion by a phosphating
treatment. Epoxy powder painted, RAL 7032 colour (other colours on
request)
External Protection Degree: IP30
Locking system By screw
Ventilation
Natural
Isolating Switch
Three-pole with door interlocking device
|
Supply
Cable entry from the top
Wiring
By N07VK CEI 20-22 flame retardant cables.
Fuses
Each bank of capacitors is protected by a set of three fuses (NH00 type)
with high breaking capacity
Capacitors
Self-healing metallized polypropylene single-phase capacitors, equipped
with overpressure safety device and discharge resistor. Filling:
biodegradable non toxic dry type, PCB free. Delta connection.
MFA
440 Vac Series, IMQ approved.
Capacitance tolerance: -5% +10%
Dielectric losses: <0.3W/kvar
Temperature class: -25/D (55°C)
Reference Standards
Comply with L.V. 73/23 (93/68) EEC Directive
Capacitors: CEI EN 60831-1/2
Equipment: CEI EN 60439-1 |
| |
|
Standard model
|
|
|
Dimensions |
Type
|
Power at
400 Vac
50 Hz |
Isolating switch |
Rated current |
Weight
|
Power at
415 Vac
50 Hz |
|
W x D x H mm
|
|
kvar |
A
|
A
|
kg
|
kvar
|
|

|
P1
325x225x380 |
QRS/44
|
5
|
25
|
7,2
|
8
|
5,5
|
|
QRS/44
|
10
|
25
|
14,4
|
9
|
11
|
|
QRS/44
|
15
|
40
|
21,6
|
10
|
16
|
|
QRS/44
|
20
|
63
|
28,8
|
12
|
22
|
|
QRS/44
|
25
|
63
|
36
|
13
|
27
|
|
QRS/44
|
30
|
80
|
43
|
15
|
32,5
|
|
P2
355x225x550 |
QRS/44
|
40
|
100
|
58
|
18
|
43
|
|
QRS/44
|
50
|
125
|
72
|
20
|
54
|
|
QRS/44
|
60
|
160
|
86
|
22
|
65
|
|
The
manufacturer reserves the right to modify data and sizes without
previous. notice. |
|
|