TCC 690 series

THREE-PHASE CYLINDRICAL CAPACITORS FOR FIXED POWER FACTOR CORRECTION

High reliability and absolute operational safety are the main features of the TCC series.

Reliability is guaranteed by the particular type of dielectric and metallization used and by the strict controls carried out on all phases of the production cycle.

Security is guaranteed by a complete range of devices:

Internal Overpressure Device: this device operates in case of internal short circuit by disconnection of the internal connections. It is necessary to allow at least 10 mm for the case expansion. Do not use rigid connections.

Internal discharge resistors are used for all capacitors of 55 mm and 65 mm diameter. External resistors are supplied for all capacitors of 75 mm, 85 mm, 100 mm, 116 mm and 136 mm diameter. The function of the discharge resistors is to reduce the voltage between terminals of the capacitor to levels prescribed in the following Specifications EN 60831/1-2 and IEC 831/1-2.

If capacitors are used as part of an automatic assembly, where a large number of switching cycles are possible, the inrush current must be limited to appropriate level, by using of suitable dumping inductors. The alternative to chokes is the using of special contactors designed for use with capacitors and provided with dumping resistors.

The TCC capacitors are made in an aluminum case with an M12 fixing shank.

The 55mm and 65mm diameter capacitors are equipped with M6 screw terminals and a plastic cap to protect against accidental contact.

Capacitors with 75mm, 85mm, 100mm, 116mm and 136mm diameter are with IP20 terminal blocks.

The TCC three-phase capacitor for low voltage Power Factor Correction complies with the following Standards: EEC 89/336 Standards (amended by EEC 92/31 – EMC) and EEC 73/232 Standards (amended by EEC 96/3 – Low Voltage).

Technical characteristics

Dielectric Metallized polypropylene film
Rated voltage 690 Vac
Rated frequency 50 Hz
Power tolerance -5% + 10%
Dielectric losses < 0,20 W/KVAr
Working ambient temperature -25°C + 55°C (D class)
Max over voltage 1,1 Un (according to IEC)
Max over current 1,3 In
Max inrush current 200 In
AC test voltage between terminals 2,15 Un for 2 sec.
AC test voltage between case/terminals 3 kV for 10 sec.
Insulation level 3/15 KV
Discharge resistors Included
Internal connection Delta three-phase
Safety device Internal overpressure disconnector
Terminals
M6 screw (ø55-65 mm) Terminal board (ø75-85-100-116-136 mm)
Fixing M12
Filling Solid non-toxic biodegradable, without PCB
Service type Continuous, indoor
Protection degree IP 20
Mounting position
Vertical preferable for better cooling
Permissible humidity 95%
Service life 100.000 hours
Reference standards CEI EN 60831-1/2 IEC 831-1/2

Standard type:

50 Hz Power Current Capacitance Diameter High Weight Discharge time (10% Un)
kvar Vac-Hz A μF D mm H mm kg Sec.
TCC 05069 5 690-50 4,2 3×11,2 75 210 1,2 10
TCC 07569 7,5 690-50 6,3 3×16,7 85 210 1,6 15
TCC 10069 10 690-50 8,4 3×22,3 100 210 2 20
TCC 12569 12,5 690-50 10,5 3×27,9 100 210 2 25
TCC 15069 15 690-50 12,5 3×33,4 116 210 2,6 30
TCC 20069 20 690-50 16,7 3×44,6 116 210 2,6 40
TCC 25069 25 690-50 20,9 3×55,7 136 210 3,2 50
TCC 30069 30 690-50 25,1 3×66,9 116 285 3,2 60
TCC 40069 40 690-50 33,5 3×89,2 136 285 3,8 80

Ø 55 – Ø 65 mm